Interpretation of the Results of Geo-electric Sounding Based on a Mathematical Model of Double-layered Soil
Scindeks Assistant SCIndeks Assistant: Journal Management System
PDF (Serbian (Latin))

How to Cite

[1]
M. Grbić, D. Salamon, and A. Pavlović, “Interpretation of the Results of Geo-electric Sounding Based on a Mathematical Model of Double-layered Soil”, Zb EI Nikola Tesla, vol. 23, no. 23, pp. 189–198, Dec. 2013, doi: 10.5937/zeint23-4544.

Abstract

This paper presents the soil resistivity testing results carried out at the location designated for the construction of substation 110/35/10 kV Zlatibor. Testing results show that the tested soil is double-layered. Interpretation of the results of geo-electric sounding based on a mathematical model of double-layered soil shows good matching with the test results.

DOI: 10.5937/zeint23-4544